Lietuviškai

Burners » Elco » Range: Tectron® E10. … GL-EUF

Range: Tectron® E10. … GL-EUF

• Two-stage progressive digital low NOx dual fuel forced draught
burner.
• Free flame low NOx class 3 technology.
• Fuel: natural gas, net calorific value 8,83 … 10,53 kWh/m3,
light oil, viscosity 6 mm2/s by 20°C, net calorific value
11,86 kWh/kg.
• Maximum heat power: 12 000 and 14 000 kW.
• Minimum / maximum power ratio:
- natural gas,1/7 (1/8 with frequency inverter),
- light oil, 1/3,5.
• Air / gas ratio with choice of two different digital control boxes:
BCS or Etamatik.
• Three flame tube lengths.
• Burner head adjustments preserved during maintenance.
• Optimal accessibility and burner head adjustments preserved
during maintenance.
• Maximum compactness, minimum weight.
• Closing of the air damper on burner shut-down.
• Control box: on request, in or out the body of the burner.
• Enumerated connection terminals in the body of the burner.
• Communication by bus with Etamatik (in progress for BCS).
• Gas train factory assembled and tested for tightness and
electrical security (definition, description and dimensions:
see options chapter).
• Three-phase electrical power supply.
• Protection level IP 40 (IP 54 as option).
• Maximum working temperature 60°C.
• In compliance with the EN 267, EN 676 norms and European
Guidelines such as:
- low voltage 73/23/EC
- EMC 2004/108/EC
- gas appliances 90/396/EC Contact form